BC Series Power Take-Off Units
Specifications/Description
Conductor Material: 1070 High-Conductivity Aluminum Busbar / T2 Red Copper Busbar
Insulated housing made of flame-retardant engineering plastic (UL94 V-0 rating)
Connection Method: Elastic Clamping + Bolt Fixing
Output terminals: aluminum busbar with tin plating/copper busbar with tin plating, bolted connection with 3–4 holes.
Heat-shrink tubing – red/black heat-shrink insulating sleeve
Protection rating IP20
Rated voltage: DC 48 V (±10%), compatible with IDC-standard server DC power supply.
Rated current: 200–1,000 A (single circuit). Common specifications: 300 A / 400 A / 500 A.
Contact resistance ≤10 μΩ, ensuring low loss and low thermal resistance under high current.
Dielectric withstand voltage: AC 2000 V for 1 minute; no breakdown between insulating parts and conductors.
Insulation class: Class B (130°C) / Class F (155°C), suitable for the ambient temperature inside the equipment cabinet.
Operating temperature: -10°C to +70°C; continuous operation inside the cabinet.
Short-time withstand current of 1000 A for 1 s meets the short-circuit current impact requirements for the project.
Keyword: BC Series Power Take-Off Units
Category:
Power take-off
More Products
Contact Us
Email:
Address:
No. 99, Jinlong Avenue, Xiaojinkou, Huicheng District, Huizhou City, Guangdong Province, China